Stuart

Stuart CH 4-60 (60Hz)

Find a Local Stockist

Find an Online Stockist

Centrifugal Horizontal Pump Multistage

The CH 4-60 centrifugal multistage pump is ideal for pressure boosting in applications where long pipe runs or high heads may be involved. CH 4-60 pumps are self priming up to 5 metres and offer a high quality, reliable solution with flow rates up to 174 litres per minute and heads up to 74 metres.

1 Year Warranty UKCA-CE
Stuart CH 4-60 (60Hz)
Key Features
  • Flow rates up to 174 litres per minute and heads up to 74 metres
  • Durable brass and stainless steel construction
  • Multistage centrifugal pump
Technical Specification
Product Code 46646
General
Warranty 1 year
Approvals CE
Features
Pump type Centrifugal Multistage
Priming vent plug
Self priming
Mechanical seal EPDM / Carbon / Ceramic
Typical noise 70 dB(A)
Materials
Pump body Brass / stainless steel
Impeller Stainless steel
Performance
Maximum head - closed valve 74 metres
Performance @ 50 l/min 72 metres
Performance @ 100 l/min 54 metres
Maximum flow 174 l/min
Minimum static inlet pressure 0.05 bar / 0.5 metres
Maximum static inlet pressure 1.0 bar / 10 metres
Maximum static outlet pressure 1.2 bar / 12 metres
Maximum working pressure* 900 kPa / 9 bar
Maximum ambient air temperature 50 °C
Min / Max water temperature** Min 4 °C / Max 65 °C
Maximum suction lift*** 5 metres
Connections
Pump connections (Inlet) G 1ΒΌ F
Pump connections (Outlet) G 1 F
Motor
Type Induction, auto-reset thermal trip
Duty rating Continuous (S1) @ 2.5 l/min and above
Electrical
Power supply (Vac/Ph/Hz) 220 V a.c. / 1 / 60 Hz
Power consumption - P1 2921 Watts
Current - full load 13.6 Amps
Fuse rating 16 Amps
Power cable length 0.75 metres (pre-wired)
Physical
Enclosure protection IPX5
Length 456 mm
Width 187 mm
Height - excluding hoses 210 mm
Weight - including fittings 17.8 Kg
GTIN 13 DIGIT 5050400466468
* The maximum pressure that can be applied to the pump under any installation conditions.
** A stored water temperature of 60 oC is considered suffiecient to meet all normal requirements and will minimise deposition of scale in hard water areas.
*** With footvalve fitted.
Although these pumps are self priming we recommend a footvalve/strainer is used if a suction lift is required.
Compare Models
Description Part Number Maximum head - closed valve Maximum flow
Stuart CH 4-30 (50Hz) 46553 25 metres 140 l/min
Stuart CH 4-40 (50Hz) 46554 36 metres 160 l/min
Stuart CH 4-50 (50Hz) 46555 50 metres 160 l/min
Stuart CH 4-60 (50Hz) 46556 62 metres 160 l/min
Stuart CH 4-30 (60Hz) 46643 27 metres 147 l/min
Stuart CH 4-40 (60Hz) 46644 42 metres 163 l/min
Stuart CH 4-50 (60Hz) 46645 56 metres 157 l/min
Stuart CH 4-60 (60Hz) 46646 74 metres 174 l/min
Videos